Each of the sections is collapsible and expandable by clicking the – and + icon to the left of the section name.Possible Device Status | Description |
On Line | The UPS is running normally on AC utility power. |
On Line (Green Mode) | The UPS is running normally on AC utility power, and the electrical input is being utilized with high efficiency. In addition, the value must be above thevalue set on when you first install PowerChuteShutdown Settings. |
Initializing | The UPS is attempting to establish communications with the UPS. |
On Battery | The UPS is using its battery to provide output power to the load. |
Low Battery | The UPS is on battery, and the “Runtime Remaining” reported by the UPS is less than the At runtime limit value on the when you first install PowerChuteShutdown Settings screen. By default, a Low Battery shutdown begins. (It is possible to reverse this setting on the Event Configuration screen). |
Battery Discharged | The UPS is on line, and the “Runtime Remaining” reported by the UPS is less than the At runtime limit value on the when you first install PowerChuteShutdown Settings screen. If you get a power outage when your battery is discharged, PowerChute immediately begins the process of gracefully shutting down your system. PowerChute can display this status immediately after a runtime calibration (which deeply discharges the battery) or when the UPS returns to On Line operation after an extended power outage. NOTE: It is possible to see this status when the “Battery Charge” under Battery Status on this screen is displaying as 100%. This can happen when the “Runtime Remaining” value falls below thevalue set on when you first install PowerChuteShutdown Settings. |
Replace Battery | The UPS battery has reached the end of its life. See Battery Management for more information. |
No Batteries Attached | Your UPS cannot detect any batteries. NOTE: For supported SRV Easy UPS models, it can take up to 10 minutes for the UPS to detect a disconnected battery. The will appear as during this time. |
UPS in Bypass* | Your UPS is in bypass mode. |
Maintenance Bypass* | Your UPS is on bypass for maintenance purposes. |
UPS Initiated Bypass* | The UPS is reporting an internal hardware issue that caused it to switch to bypass operation. For further information, see the support services at www.apc.com/support. |
User Initiated Bypass* | A user requested bypass operation through either the PowerChute Serial Shutdown or the UPS LCD user interface. |
Bypass* Power Supply Fault | The UPS auxiliary power supply is not functioning. For further information, see the support services at www.apc.com/support. NOTE: If you try to put the UPS on bypass while this condition exists, the UPS loses all output power and the connected load shuts off. |
Overloaded | The UPS cannot support the current load. Unplug some equipment to reduce the load. If the UPS still indicates an overload, see the support services at www.apc.com/support. |
AVR Boost Active | The UPS is using AVR Boost (Automatic Voltage Regulator) to correct a low input voltage without switching to battery power. |
AVR Trim Active | The UPS is using AVR Trim to correct a high input voltage without switching to battery power. |
Performing Self Test | The UPS is performing a self test, see Diagnostics. |
Performing Calibration | The UPS is performing a runtime calibration, see Diagnostics. |
Sleeping | One or more outlets on your UPS are turned off but are scheduled to turn on. |
Unknown | The status of the UPS is unknown. |
UPS Communication Lost | The PowerChute Agent has lost communications with the UPS. Make sure that the UPS cable is securely connected at both ends. |
UPS Off | Your UPS is turned off. |
Field | Description |
UPS Load | In watts, the power supplied by the UPS as a percentage of its full rating. |
Runtime Remaining | The amount of time the UPS — while on battery — could support the present load. The value is shown in minutes. NOTE: The maximum value of this field varies depending on the communication method used with PowerChute. If USB connection is used, the maximum value that will be shown is 1092. Whereas if serial connection is used, the maximum value is 9999. |
Internal Temperature | The temperature inside the UPS. |
Load Power | In VA, volt-ampere, the power supplied by the UPS as a percentage of its full rating. |
Load Current | The current drawn from the UPS by the connected equipment. |
Field | Description |
Battery Charge | The present charge of the UPS battery, as a percentage of the total possible capacity. |
Battery Voltage | The present voltage of the UPS battery. |
Total Battery Packs | This is only reported for some UPS types. It states the number of battery packs connected to your UPS. |
Some fields described in this section do not display for every UPS and configuration.Field | Description |
Battery Status | The possible values here are , , and . NOTE: For supported SRV Easy UPS models, it can take up to 10 minutes for the UPS to detect a disconnected battery. The will appear as during this time. If you need to replace your battery, see Battery Part Number below. |
Battery Charge | The present charge of the UPS battery, as a percentage of the total possible capacity. |
Battery Voltage | The present voltage of your UPS battery (as distinct from AC utility power) in volts DC. |
Runtime Remaining | The amount of time the UPS battery could support its load. |
Battery Part Number | This part number is essential for re-ordering. Click on the link to go to a web page where you can buy a new battery for your UPS online. If a part number is not shown for your UPS device, the link will take you to a web page where you can enter your UPS model number to find the correct replacement battery for your device. |
Field | Description |
Battery Installation Date | This displays the date that your UPS battery was installed. For some UPS devices, this information is derived from the UPS itself. For other devices you can input an installation month and year. |
Replacement Battery | This part number is essential for re-ordering. |
NOTE: Type B UPS models connected to a PowerChute Serial Shutdown Agent report ‘Passed’ for a successful Runtime Calibration test, and ‘Aborted’ for an unsuccessful test. To find out if your UPS is a Type B model, visit Knowledge Base article FA315835.Field | Description |
On UPS start-up | The UPS performs a self test when it turns on. |
On UPS start-up and every 7 days since start-up date | The UPS performs a self test when it turns on and subsequently performs a test every 7 days. (The dates do not deviate from the 7-day interval unless you turn the UPS off and then on again). For example, you turn on the UPS on September 3, so it performs a self test at turn-on and subsequently on Sept. 10, Sept. 17, Sept. 24, etc. |
On UPS start-up and every 14 days since start-up date | The UPS performs a self test when it turns on and subsequently performs a test every 14 days. See the example in the row above. |
On UPS start-up and every 7 days since last test | The UPS performs a self test when it turns on and subsequently performs a test every 7 days. However, if you manual initiate a self test, using this screen or directly on the UPS, this changes the dates (in contrast to the second item in the drop-down box where the dates would not change). For example, you turn on the UPS on September 3, so it performs a self test at turn-on and subsequently on Sept. 10. You then initiate a manual self test on Sept. 12, and the 7-date intervals continue on Sept. 19, Sept. 26, etc. |
On UPS start-up and every 14 days since last test | The UPS performs a self test when it turns on and subsequently performs a test every 14 days. However, if you manual initiate a self test, using this screen or directly on the UPS, this changes the dates. See an example in the row above. |
Test Status | Description |
In Progress | The diagnostic test is ongoing. |
Passed | The self test passed. This is not relevant for the other tests: alarm test and calibration |
Failed | Your self test, alarm test, or calibration did not succeed. |
Refused | Your UPS refused the diagnostic test. For a calibration, this will happen when the load on the UPS is less than 10% of its full capacity. In addition, for a calibration the UPS battery must be fully charged. For a self test on a Type B UPS model connected to a PowerChute Serial Shutdown Agent via USB, this will happen when there is system status of Battery Discharged. |
Aborted | Your self test, alarm test, or calibration could not run to completion because something stopped it, for example, a power outage, or it was canceled by a user. |
Completed | Your runtime calibration has finished successfully. |
Unknown | The status of your diagnostic test is unknown. This could be caused by a communication issue. |
The options explained below do not display for all UPS devices. Only supported options will be displayed for your UPS model.Field | Description |
Output Voltage1 | The voltage the UPS will supply when operating on battery power. NOTE: For some UPS models, you can only change this setting on the UPS directly. |
Upper Bypass Limit2 | When operating in bypass, this is the highest voltage the UPS will supply to the connected load. |
Lower Bypass Limit | When operating in bypass, this is the lowest voltage the UPS will supply to the connected load. |
High Transfer Voltage | On UPS devices that do NOT support bypass, this is the highest voltage the UPS will supply to the connected load. NOTE: On UPS devices that support AVR Trim, it will be reported when the Input Voltage is higher than this value. |
Low Transfer Voltage | On UPS devices that do NOT support bypass, this is the lowest voltage the UPS will supply to the connected load. NOTE: On UPS devices that support AVR Boost, it will be reported when the Input Voltage is lower than this value. |
Sensitivity | The sensitivity of the UPS to distortions in the line voltage. |
The options explained below do not display for all UPS devices. Only supported options will be displayed for your UPS model.Field | Description |
UPS Name | A user-customizable name for the UPS. You can use US-ASCII characters only, codes 32-126. NOTE: Depending on the UPS type, a maximum of between 8 to 16 alphanumeric characters is allowed. The PowerChute Server Description in the top-left corner of the UI defaults to the UPS Name. This description is user-customizable and if edited, it will override the UPS Name. |
Audible Alarm | With this field, you can enable or disable the UPS audible alarm that sounds in response to power problems. On the top right of your screen, one of the following three alarm icons displays: The alarm is enabled. The alarm is disabled. Your system has lost communications with your UPS. |
UPS Output Load Threshold | Each UPS has a maximum rating, for example, 1500 VA. Use this field to set the preferred highest percentage of this rating used by the load. For example if this threshold is set to 70(%), when the load consumes more then 1050 VA (70% of 1500), the Output Load Threshold Exceeded event is generated. |
High Internal Temp Threshold | When this temperature is exceeded, an UPS Internal Temperature Threshold Exceeded event is generated. (By default, this event causes a shutdown). This temperature should be greater than (or at least equal to) the High Internal Temp Warning Threshold in the row below. NOTE: Set this value above the normal temperature range of the UPS. If you don’t, the Internal Temperature Exceeds Critical Range event will be continually generated. To troubleshoot this, see UPS Internal Temperature Threshold Exceeded. |
High Internal Temp Warning Threshold | When this temperature is exceeded, a UPS Internal Temperature Warning event is generated. |
The options explained below do not display for all UPS devices. Only supported options will be displayed for your UPS model.Status | Description |
Acceptable | Input voltage is within the bypass limits. The UPS can be placed into bypass mode. |
Pending Acceptable | Input voltage is marginally outside the bypass limits. |
Voltage Too High | Input voltage is above the upper bypass limit. |
Voltage Too Low | Input voltage is below the lower bypass limit. |
Distorted | Input voltage is distorted. |
Action | Description |
Put in Bypass | This option is available when the UPS is not in bypass mode. |
Return from Bypass | This option is available when the UPS is in bypass mode. |